Project Description

FDB5-24


Description

Flameproof surge arrester for protecting two 24 V interfaces in potentially explosive atmospheres. Application: Flow sensors, temperature sensors.

  • Easy to mount on the spare cable gland of field devices
  • Flexible use in Ex(i) and Ex(d) circuits
  • Installation in conformity with the lightning protection zone concept at the boundaries from 0B-2 and higher
SEND INQUIRY
PDF Download
TypeFDB5-24
SPD according to EN 61643-21 / IEC 61643-21type 2 / class II
Nonimal voltage Un24 V
Max. continuous operating a.c. voltage Uc25.4 V
Max. continuous operating d.c. voltage Uc36 V
Nominal current IL0.55 A
D1 Lightning impulse current (10/350 μs) line-PG (Iimp)1.5 kA
C2 Total nominal discharge current (8/20 μs) (In)20 kA
C2 Nominal discharge current (8/20 μs) line-PG (In)10 kA
Voltage protection level line-line for In C2 (Up)≤ 65 V
Voltage protection level line-PG for In C2 (Up)≤ 2000 V
Voltage protection level line-line at 1 kV/μs C3 (Up)≤ 50 V
Voltage protection level line-PG at 1 kV/μs C3 (Up)≤ 1200 V
Capacitance line-line (C)≤ 2 nF
Capacitance line-PG (C)≤ 15 pF
Range of operating temperatures (TU)-40/+80°C
Degree of protectionIP67
For mounting on (field / device side)M20 x 1.5 male thread
Connectionconnecting lines (1.3 mm2)
Length of the connecting lineApprox. 150 mm
Earthing viaconnecting line
Enclosure materialstainless steel