Surge Arrester – Type 1+Type 2

FLP25-275/1

Integral housing lightning current and surge arrester for protecting power supply system against surges.

  • Prewired spark-gap-based type 1 and type 2 combined lightning current and surge arrester
  • Maximum system availability due to RADAX Flow follow current limitation
  • Capable of protecting terminal equipment
surge-protective-device-flp25-275-1
dimensions-flp25-275-1
Dimensions
basic-circuit-diagram-flp25-275-1
Basic circuit diagram

Technical data

TypeFLP25-275/1
SPD according to EN 61643-11 / IEC 61643-11type 1 + type 2 / class I + class II
Nominal a.c. voltage Un275 V AC (48/62 Hz)
Max. continuous operating a.c. voltage Uc320 V AC (48/62 Hz)
Nominal discharge current (8/20μs) In60 kA
Maximum discharge current (8/20μs) Imax100 kA
Lightning impulse current (10/350μs) Iimp25 kA
Voltage Protection level Up2,0 kV
Response time tA100 ns
Follow current extinguishing capability Ifi50 kArms
Max. backup fuse (L) up to IK = 50 kArms315 A gL/gG
Max. backup fuse (L-L’)125 A gL/gG
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic440 V / 120 min. – withstand
Range of operating temperatures (TU)-40/+80°C
Operating state / fault indication
Number of ports1
Cross-sectional area (L1, L1′, L2, L2′, L3, L3′, N, N’, PE) (min.)10 mm2 solid /flexible
Cross-sectional area (L1, L2, L3, N, PE) (max.)50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (L1′, L2′, L3′, N’, PE) (max.)35 mm2 stranded / 25 mm2 flexible
For mounting on35 mm DIN rail acc. to EN 60715
Enclosure materialthermoplastic
Place of installationindoor installation
Degree of protectionIP20
Capacity2 module(s), DIN 43880
Approvals
Type of remote signalling contact
a.c switch capacity
d.c switch capacity

Downloads:

Other products in this category 


surge-arrester-flp25-275-11

FLP25-275/1+1

Un = 275 Vac

Iimp (10/350μs) = 25 kA

1+NPE, single-phase, for TT and TN systems

surge-arrester-flp25-275-2

FLP25-275/2

Un = 275 Vac

Iimp (10/350μs) = 25 kA

2P, single-phase, for TN systems

surge-arrester-flp25-275-3

FLP25-275/3

Un = 275 Vac

Iimp (10/350μs) = 25 kA

3P, three-phase, for TN-C systems

surge-arrester-flp25-275-31

FLP25-275/3+1

Un = 275 Vac

Iimp (10/350μs) = 25 kA

3+NPE, three-phase, for TT and TN-S systems

surge-arrester-flp25-275-4

FLP25-275/4

Un = 275 Vac

Iimp (10/350μs) = 25 kA

4P, three-phase, for TN-S systems