Project Description

LSA-A-LEI


Description

SPD block for ten pairs with three-pole gas discharge tubes for telecommunications distribution systems, the LSA surge voltage components offer rapid, adequate protection. The LSA system offers both basic protection modules and fine protection modules to protect up to ten three-core wires per connection strip. Thus it can be immediately identified whether an arrester has to be replaced.

  • SPD block for ten pairs with three-pole gas discharge tubes
  • Bandwidth-optimised for secure transmission
  • For installation in conformity with the lightning protection zone concept at the boundaries from 0B–1 and higher
SEND INQUIRY
PDF Download
TypeLSA-A-LEI
SPD according to EN 61643-21 / IEC 61643-21type 2 / class II
Nominal a.c. voltage Un110 V
Max. continuous operating d.c. voltage Uc180 V
Max. continuous operating a.c. voltage Uc127 V
Nominal current (IL)0.4 A
Nominal discharge current (8/20μs) In5 kA
Maximum discharge current (8/20μs) Imax10 kA
Overstressed fault mode10 kA (8/20μs ): open line EN 61643-21: mode 3
Impulse resetno backup fuse under nominal conditions
Voltage protection level line-PG for Iimp 10/350 μs D1 (UP)≤ 600 V
Voltage protection level line-line for In C2 (UP)≤ 600 V
Voltage protection level line-PG for In C2 (UP)≤ 600 V
Voltage protection level line-line for 1 kV/μs C3 (UP)≤ 600 V
Voltage protection level line-line for 1 kV/μs (UP)≤ 600 V
Capacitance line-line (C)≤ 5 pF
Capacitance line-PG (C)≤ 5 pF
Range of operating temperatures (TU)-40/+80°C
Fail-safe function–
Pluggable intoLSA disconnection and terminal blocks (type 2)
Earthing viamounting frame
Enclosure materialpolyamide
Colorgrey
Accessory for LSA-A-LEI
Gas Discharge Tube
High-capacity replacement gas discharge tubes for LSA-A-LEI. Three-pole unit for a constant voltage protection level line-line and line-ground.
TypeGDT-230-G3 / 3RM230L-8
Nominal discharge current (8/20μs) In5 kA
Design8.0mm×10.0mm

Dimensions-and-Basic-circuit-diagram-SPDs-for-LSA-Technology-LSA-A-LEI