SPDs for Telecommunication and Data  Networks

ND-CAT 6A/EA

The “Net Defender” permits the use of Power over Ethernet with nominal currents of up to 1 A. It can be snapped directly onto the hat rail and uses it to create the necessary equipotential bonding. Alternatively, terminal protection using a separately connectable

  • Support for Power over Ethernet + up to 1 A (PoE+ according to IEEE 802.3at)
  • CAT 6A in the channel according to ANSI/TIA/EIA-568
  • For installation in conformity with the lightning protection zone concept at the boundaries from 0B-2 and higher
IT-Systems-Net-Defender-ND-CAT-6AEA
dimensions-nd-cat-6aea
Dimensions
basic-circuit-diagram-nd-cat-6aea
Basic circuit diagram

Technical data

TypeND-CAT 6A/EA
SPD according to EN 61643-21 / IEC 61643-21type 2 / class II
Max. continuous operating a.c. voltage Uc41 V
Max. continuous operating d.c. voltage Uc58 V
Max. continuous operating d.c. voltage pair-pair (PoE) Uc57 V
Rated current IL1 A
D1 Lightning impulse current (10/350 μs) per line Iimp1 kA
C2 Nominal discharge current (8/20 μs) line-line In150 A
C2 Nominal discharge current (8/20 μs) line-PG In2.5 kA
C2 Total nominal discharge current (8/20 μs) line-PG In10 kA
C2 Nominal discharge current (8/20 μs) pair-pair (PoE) In150 A
Voltage protection level line-line for In C2 UP< 190 V
Voltage protection level line-PG for In C2 UP< 600 V
Voltage protection level pair-pair for In C2 (PoE) UP< 600 V
Voltage protection level line-line at 1 kV/μs C3 UP< 145 V
Voltage protection level line-PG at 1 kV/μs C3 UP< 500 V
Voltage protection level pair-pair at 1 kV/μs C3 (PoE) UP< 600 V
Insertion loss at 250 MHz< 2 dB
Capacitance line-line (C)< 165 pF
Capacitance line-PG (C)< 255 pF
Range of operating temperatures (TU)-40/+80°C
Degree of protectionIP 20
Connection (input / output)RJ45 / RJ45
Pinning1/2, 3/6, 4/5, 7/8
Enclosure materialAluminum housing
Earthing viaConnecting line
Transmission class according to ISO/IEC 11801Cat. 6
Transmission class according to EN 50173-1Class EA
Transmission class according to ANSI/TIA/EIA-568Cat. 6A in the channel

Downloads:

Other products in this category


RJ11S-TELE

The data cable protection devices for telecommunications applications are available as combination protection and fine protection.

RJ45S-E100

Protection devices are mounted in an aluminium housing with Sub RJ45 connector and can be mounted simply as an adapter connector.

RJ45-E100

Protection devices are mounted in an aluminium housing with Sub RJ45 connector and can be mounted simply as an adapter connector.

RJ45-E100-8U

Protection devices are mounted in an aluminium housing with Sub RJ45 connector and can be mounted simply as an adapter connector.

RJ45-E100-16U

ADSL/PSTN surge protection;  RJ45 connector; 19″ inches rackmount

Surge protector RJ45S-E100-24U

RJ45-E100-24U

ADSL/PSTN surge protection;  RJ45 connector; 19″ inches rackmount