Best practice for using Surge protection devices (SPDs) and RCD together

Surge protection devices (SPDs) and RCDs


Where the power distribution system incorporates RCDs transient activity could cause RCDs to operate and hence loss of supply. Surge protective devices (SPDs) should wherever possible be installedĀ upstream of RCD to prevent unwanted tripping caused by transient overvoltages.

Where surge protective devices are installed in accordance withĀ BS 7671Ā 534.2.1 and are on the load side of a residual current device, anĀ RCD having an immunity to surge currentsĀ of at least 3 kA 8/20, shall be used.

IMPORTANT NOTESĀ //Ā S type RCDsĀ satisfy this requirement. In the case of surge currents higher than 3 kA 8/20, the RCD may trip causing interruption of the power supply.

If the SPD is installed downstream of the RCD, the RCD should be of the time delayed type with an immunity to surge currents of at least 3kA 8/20.Ā Section 534.2.2 of BS 7671 details the minimum SPD connection requirements (based on the SPD modes of protection) at the origin of the installation (typically a Type 1 SPD).

In case you are not familiar with surge protective devices operation and types, you better read firstĀ the basics of surge protective devices.

SPD connection type 1 (CT1)

An SPD configuration based on connection type 1 (CT1) is forĀ TN-C-SĀ orĀ TN-S earthing arrangementsĀ as well the TT earthing arrangementĀ where the SPD is fitted downstream of the RCD.

spds-installed-load-side-rcd

Figure 1 ā€“ Surge protective devices (SPDs) installed on load side of RCD

In general, TT systems require special attention because they normally have higher earth impedances which reduce earth fault currents and increases the disconnection times ofĀ Overcurrent Protective Devices ā€“ OCPDs.

Therefore in order to meet the requirements for safe disconnection times, RCDs are used forĀ earth fault protection.

SPD connection type 2 (CT2)

An SPD configuration based on connection type 2 (CT2) is required on aĀ TT earth arrangementĀ if the SPD is upstream of the RCD. The RCD being downstream of the SPD would not operate should the SPD become defective.

spds-installed-supply-side-rcd

FigureĀ 2 ā€“Ā Surge protective devices (SPDs) installed on supply side of RCD

The SPD arrangement here is configured such that the SPDs are applied between the live conductors (live to neutral) rather than between live conductors and the protective conductor.

Should the SPD become defective it would, therefore, create aĀ short circuit current rather than an earth fault current and as such would ensure that the overcurrent protective devices (OCPDs) in-line with the SPD safely operate within the required disconnection time.

A higher energy SPD is usedĀ between neutral and the protective conductor. This higher energy SPD (typically a spark-gap for a Type 1 SPD) is required as lightning currents arise towards the protective conductor and as such this higher energy SPD sees up to 4 times the surge current of the SPDs connected between the live conductors.

Clause 534.2.3.4.3, therefore, advises that the SPD between neutral and the protective conductor is rated at 4 times the magnitude of the SPD between the live conductors.

Therefore,Ā only if the impulse current IimpĀ cannot be calculated, 534.2.3.4.3 advises that the minimum value Iimp for an SPD between neutral and the protective conductor is 50kA 10/350 for a 3 phase CT2 installation, 4 times 12.5kA 10/350 of the SPDs between theĀ live conductors.

The CT2 SPD configuration is often referred the ā€˜3+1ā€™ arrangement for a 3 phase supply.

SPDs and TN-C-S earth configurations

The minimum SPD connection requirements at or near the origin of the installation for a TN-C-S system requires further clarification as Section 534 of BS 7671 illustrates (see Figure 3 below) a Type 1 SPD being required between the live and PE conductors ā€“ the same as required for a TN-S system.

installation-surge-protective-devices-spds

FigureĀ 3 ā€“Ā Installation of Types 1, 2 andĀ 3 SPDs, for example in TN-C-S systems

The termĀ ā€˜at or near the origin of the installationā€™Ā creates ambiguity given the fact that the word ā€˜nearā€™ is not defined. From a technical point of view, if SPDs are applied within a 0.5m distance of the PEN split to separate N and PE, there is no need to have an SPD protection mode between N and PE as shown in the figure.

If BS 7671 would allow the application of SPDs to the TN-C side (utility side) of the TN-C-S system (observed in some parts of Europe), then it may be possible to install SPDs within 0.5m of the PEN split to N and PE and omit the N to PE SPD protection mode.

However as SPDs can only be appliedĀ the TN-S side (consumer side) of the TN-C-S system,Ā and given SPDs are typically installed at the main distribution board, the distance between the SPD installation point and the PEN split will almost always beĀ greater than 0.5 m,Ā so there is a need to have an SPD between N and PE as required for a TN-S system.

As Type 1 SPDs are specifically installed to prevent the risk of loss of human life (to BS EN62305) through dangerous sparking which could present a fire hazard for example, in the interests of safety alone, the engineering judgement is that an SPD should be fitted between N and PE for a TN-C-S system as it would in a TN-S system.

In summary, as far as Section 534 is concerned,Ā TN-C-S systems are treated the same as TN-S systems for the selection and installation of SPDs.

The basics ofĀ surge protection devices

A Surge Protection Device (SPDs) is a component of the electrical installation protection system. This device is connected to the power supplyĀ in parallel with the loads (circuits)Ā that it is intended to protect (see Figure 4). It can also be used at all levels of the power supply network.

This is the most commonly used andĀ most practical type of overvoltage protection.

The principle of Surge Protection Operation

SPDs are designedĀ to limit transient overvoltages due to lightning or switchingĀ and divert the associated surge currents to earth, so as to limit these overvoltages to levels that are unlikely to damage the electrical installation or equipment.

surge-protection-device-spd-protection-system-parallel

Types of surge protection devices

There are three types of SPD according to international standards:

Type 1 SPD

Protection against transient overvoltagesĀ due to direct lightning strokes.Ā The Type 1 SPD is recommended to protect electrical installations against partial lightningĀ currents caused by direct lightning strokes. It can discharge the voltage from lightningĀ spreading from the earth conductor to the network conductors.

Type 1 SPD is characterised by aĀ 10/350Āµs current wave.

Figure 5 ā€“ Three types of SPD according to international standards

Type 2 SPD

Protection against transient overvoltagesĀ due to switching and indirect lightning strokes.Ā The Type 2 SPD is the main protection system for all low voltage electrical installations.Ā Installed in each electrical switchboard, it prevents the spread of overvoltages in theĀ electrical installations and protects the loads.

Type 2 SPD is characterised by anĀ 8/20Āµs current wave.

Type 3 SPD

Type 3 SPDĀ is usedĀ forĀ local protection for sensitive loads.Ā These SPDs have a low discharge capacity. They must therefore only be installed as aĀ supplement to Type 2 SPD and in the vicinity of sensitive loads. They are widely availableĀ as hard-wiredā€™ devices (frequently combined with Type 2 SPDs for use in fixed installations).

However, they are also incorporated in:

  • Surge protected socket outlets
  • Surge protected portable socket outlets
  • Telecoms and Data protection