Project Description

COAX-BNC-8U F/F


Description

Surge arrester with BNC for protecting Closed Circuit Television (CCTV), video, camera, and surveillance systems to avoid being influenced by leakage pickups.

  • Easily adaptable due to BNC sockets
  • For installation in conformity with the lightning protection zone concept at the boundaries from 0B – 2 and higher
  • Application: CCTV, video, camera and surveillance systems
SEND INQUIRY
PDF Download
TypeCOAX-BNC-8U F/F
SPD according to EN 61643-21 / IEC 61643-21type 2 / class 2
Nominal a.c. voltage Un5 V
Max. continuous operating a.c. voltage Uc6.2 V
Rated current (IL)0.1 A
D1 Lightning impulse current (10/350μs) Iimp1 kA
C2 Nominal discharge current (8/20μs) shield-PG In10 kA
C2 Nominal discharge current (8/20μs) line-shield In5 kA
Voltage protection level line-shield for In C2 UP< 35 V
Voltage protection level line-PG for In C2 UP–
Voltage protection level line-shield at 1 kV/μs C3 UP< 13 V
Voltage protection level line-PG at 1 kV/μs C3 UP–
Frequency range0 – 300 Mhz
Insertion loss at 160 Mhz< 0.4 dB
Insertion loss at 300 Mhz< 3 dB
Return loss at 130 Mhz> 20 dB
Return loss at 300 Mhz> 8 dB
Characteristic impedance (Z)50 ohms / 75 ohms
Series resistance per line4.7 ohms
Capacitance line-shield (C)< 25 pF
Capacitance line-PG (C)–
Range of operating temperatures (TU)-40/+80°C
Degree of protectionIP 10
For mounting onno
Lightning protection zone LPZ0B – 2
Connection (input / output)BNC female / BNC female
Earthing viaoutgoing earth conductor (0.75 mm2)
Enclosure materialAluminum housing
Colorblue, green, silvery grey

Dimensions-and-Basic-circuit-diagram-SPDs for Coaxial Connection-COAX-BNC-8U-FF