Project Description

FLP25-275/2S+1


Description

Location of Use: Main Distribution Boards
Network Systems: TT, TN-S
Mode of Protection: L-N / L′-N, N-PE
Surge Ratings: Iimp = 25 kA / 100 kA (10/350 μs), In =25 kA / 100 kA (8/20 μs)
IEC/EN Category: Class I+II / Type 1+2
Protective Elements: High Energy MOV and GDT
Housing: Monoblock Design
Compliance: IEC 61643-11:2011, EN 61643-11:2012