Project Description

FLP50GR-320/3


Description

Integral housing coordinated lightning current and surge arrester for protecting three-phase TN-C systems against surges.

  • Coordinated spark-gap-based lightning current and surge arrester
  • Maximum systems availability due to RADAX Flow follow current limitation
  • Capable of protecting terminal equipment
SEND INQUIRY
PDF Download
TypeFLP50GR-320/3
SPD according to EN 61643-11 / IEC 61643-11type 1 / class I
Nominal a.c. voltage (Un)230 / 400 V AC (50/60 Hz)
Max. continuous operating a.c. voltage (Uc)320 V AC (50/60 Hz)
Lightning impulse current (10/350μs) [L1+L2+L3-PEN] (Itotal)150 kA
Specific energy [L1+L2+L3-PEN ] (W/R)2,5 MJ/ohms
Lightning impulse current (10/350μs) [L-PEN] (Iimp)50 kA
Specific energy [L-PEN ] (W/R)625,00 kJ/ohms
Nominal discharge current (8/20μs) [L/PEN]/[L1+L2+L3-PEN ] (In)50 kA / 150 kA
Voltage protection level [L-PEN] (Up)2,0 kV
Follow current extinguishing capability a.c. (Ifi)50 kArms
Follow current limitation / Selectivityno tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Response time (tA)< 100 ns
Max. backup fuse (L) up to IK = 50 kArms (ta < 0,2 s)500 A gL/gG
Max. backup fuse (L) up to IK = 50 kArms (ta < 5 s)315 A gL/gG
Max. backup fuse (L) up to IK > 50 kArms200 A gL/gG
Max. backup fuse (L-L’)125 A gL/gG
Temporary overvoltage (TOV) (UT) – Characteristic530 V / 120 min. – withstand
Range of operating temperatures [parallel] / [series] (TU)-40…+80°C / -40…+60°C
Operating state / fault indication
Number of ports1
Cross-sectional area (L1, L1′, L2, L2′, L3, L3′, PEN) (min.)10 mm2 solid /flexible
Cross-sectional area (L1, L2, L3, PEN) (max.)50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (L1′, L2′, L3′) (max.)35 mm2 stranded / 25 mm2 flexible
For mounting on35 mm DIN rail acc. to EN 60715
Enclosure materialthermoplastic
Place of installationindoor installation
Degree of protectionIP20
Capacity6 module(s), DIN 43880
ApprovalsCE