Project Description

SLP40-PV1000/3S DC 1000V Surge Protection Device for Solar PV System


Description

Pluggable modular multi-pole DC 1000V Surge Protection Device for Solar PV System, Type 2 Class II Class C with changeover contact, compliance to EN 50539-11

  • With remote signaling contact for monitoring device (floating changeover contact) (S)
  • For installation in the DC circuits of solar photovoltaic systems, string box, inverter
  • Mode of Protection: (DC+) – PE, (DC-) – PE, (DC+) – (DC-)
  • EU Category: Type 2
  • Protective Elements: High Energy MOV
SEND INQUIRY
PDF Download
TypeSLP40-PV1000/3SLP40-PV1000/3S
SPD according to EN 50539-11:2013type 2type 2
Maximum PV voltage UCPV≤ 1000 V≤ 1000 V
Short-circuit current rating ISCPV200 A200 A
Nominal discharge current (8/20μs) In20 kA20 kA
Maximum discharge current (8/20μs) Imax40 kA40 kA
Voltage protection level UP4,0 kV4,0 kV
Response time tA25 ns25 ns
Range of operating temperatures (TU)-40/+80°C-40/+80°C
Operating state / fault indicationgreen / redgreen / red
Number of ports11
Cross-sectional area (min.)1.5 mm2 solid /flexible1.5 mm2 solid /flexible
Cross-sectional area (max.)35 mm2 stranded / 25 mm2 flexible35 mm2 stranded / 25 mm2 flexible
For mounting on35 mm DIN rail acc. to EN 6071535 mm DIN rail acc. to EN 60715
Enclosure materialthermoplasticthermoplastic
Place of installationindoor installationindoor installation
Degree of protectionIP 20IP 20
Capacity3 module(s), DIN 438803 module(s), DIN 43880
ApprovalsCECE
Type of remote signaling contactchangeover contact
a.c. switching capacity250V / 0.5 A
d.c. switching capacity250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signalling terminalsmax. 1.5 mm2 solid / flexible

ac spd details 1

Dimensions-and-Basic-circuit-diagram-SPD-SLP40-PV1000-3S