Mbongkar DG M 275 ACI, kanggo kasedhiyan sistem paling dhuwur - DEHNguard ACI


DEHNguard M TT ACI 275 FM
Arrester surge modular karo Advanced Circuit Interruption (ACI) kanggo sistem TT lan TN-S (konfigurasi 3 + 1).
Bagéan Nomer 952341 DG M TT ACI 275 FM
GTIN 4013364376632, No Customstariff.: 85363030, Grossweight: 455g

DEHNguard DG M TT ACI 275 FM (952 341)

952341 + 440m_E

Diagram sirkuit dhasar DG M TT ACI 275 FM

DEHNguard M TNS ACI 275 FM
Arrester surge modular karo Advanced Circuit Interruption (ACI) kanggo sistem TN-S.
Bagean Nomer 952440 DG M TNS ACI 275 FM
GTIN 4013364376625, No tarif pabean: 85363030, Bobot reged: 450g

DEHNguard DG M TNS ACI 275 FM (952 440)

952341 + 440m_E

Diagram sirkuit dhasar DG M TNS ACI 275 FM

DEHNguard DG MOD ACI 275 - No. 952 524

DEHNguard DG MOD ACI 275 - No. 952 524

DEHNguard DG MOD HA NPE - No. 952 083

DEHNguard DG MOD HA NPE - No. 952 083

DEHNguard modular karo Advanced Circuit Interruption (Aman Dimensi)

  • Teknologi anyar "Advanced Circuit Interruption" (ACI) terintegrasi karo modul proteksi, kalebu kombinasi switch / spark
  • Amarga teknologi ACI, ora dibutuhake sekring eksternal
  • Salib-bagean sambungan cilik (6 mm² Cu) pancen cukup *)
  • TOV tahan uga ing 440 V (AC)
  • Keandalan sistem sing dhuwur, ora ana gangguan sekering 32 GG
  • Arus bocor nol amarga isolasi galvanis dening unit saklar ACI
  • Koordinasi energi karo liyane sing nyekel kulawarga produk Red / Line
  • Geter lan uji coba kejut miturut EN 60068-2

*) Kabeh konduktor langsung kudu dipasang kabel supaya bisa mbukak sirkuit lan kesalahan bumi

ACI: Tingkat keamanan paling dhuwur

Dilengkapi kanggo mbesuk: Perlindhungan mundhak karo teknologi ACI

Teknologi ACI anyar - Gangguan Sirkuit Lanjut - nambah keamanan sistem listrik sampeyan.

Anyar: Kombinasi interval switch / spark ing tipe 2 arrester DEHNguard ACI nggawe sekring hulu superfluous. Amarga sekring serep ora dibutuhake maneh, sampeyan bakal ngirit wektu, papan, lan materi.

Bonus liyane: sampeyan ngilangi kesalahan konfigurasi sing bisa ditindakake nalika milih lan ngukur dimensi sekering serep sing cocog.

Ngurangi biaya lan sistem sampeyan aman!

Kanggo kasedhiyan paling dhuwur - supaya sistem tetep aktif

Kombinasi switch / spark gap ing DEHNguard ACI disambungake kanthi seri karo varistor. Ing pungkasan umur layanan arrester lonjakan ACI, samubarang kesalahan saiki diganggu dening varistor liwat kombinasi switch / spark interval sing disambungake ing seri lan dikurangi nganti ukuran sing paling cilik ing sistem kasebut ora bisa kesasar.

Iki tegese kasedhiyan luwih akeh lan keamanan operasional kanggo sistem yen dibandhingake karo standar tipe 2 sing nyekel sekring eksternal.

Solusi standarTeknologi CITeknologi ACI
Dimensi aman--
Salib sambungan cilik - mung 6mm2 tansah cekap--
Umur layanan sing luwih dawa amarga tahan TOV lan arus bocor nol--
Ngawasi proteksi arus kas-
Luwih akeh ruangan ing kabinet switchgear-
Ora perlu sekring eksternal-
Kontrol Dinamis Thermo
Efek proteksi arrester tipe 2

data Technical

SPD miturut EN 61643-11 / IEC 61643-11jinis 2 / kelas II
Koordinasi energi karo peralatan terminal (≤ 10 m)ketik 2 + jinis 3
Voltase ac nominal (UN)230/400 V (50/60 Hz)
Maks. voltase operasi terus (ac) [LN] (UC)275 V (50/60 Hz)
Maks. voltase operasi terus-terusan (ac) [N-PE] (UC)255 V (50/60 Hz)
Arus debit nominal (8/20 µs) [LN] (In)20 kA
Arus debit nominal (8/20 µs) [N-PE] (In)80 kA
Tingkat proteksi voltase [LN] / [N-PE] (UP)≤ 1.5 / ≤ 1.5 kV
Tingkat proteksi voltase [LN] / [N-PE] jam 5 kA (UP)≤ 1,5 / ≤ 1,5 kV
Tindakake kemampuan pemadam saiki [N-PE] (Ifi)100 Senjata
Wektu respons [LN] (tA)≤ 100 ns
Wektu respons [N-PE] (tA)≤ 100 ns
Sekring eksternal tambahanora dibutuhake
Kapabilitas tahan jangka pendek (ISCCR)25 kArms
Overvoltage Temporary (TOV) [LN] (UT) - Karakteristik440 V / 120 mnt. - tahan
Overvoltage Temporary (TOV) [N-PE] (UT) - Karakteristik1200 V / 200 ms - tahan
Kisaran suhu operasi (TU)-40 ° C… +80 ° C
Indikasi negara / kesalahanijo / abang
Jumlah port1
Area penampang (min.)1.5 mm2 padhet / fleksibel
Area silang (maks.)35 mm2 terdampar / 25 mm2 fleksibel
Kanggo sing soyo tambah35 mm DIN rol acc. nganti EN 60715
Bahan pajanantermoplastik, abang, UL 94 V-0
Papan instalasiinstalasi njero ruangan
Degree of protectionIP 20
kapasitas4 modul, DIN 43880
PersetujuanKEMA
Jinis kontak sinyal adohkontak ganti
Kapasitas saklar (ac)250 V / 0.5 A
Kapasitas ngoper (dc)250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Area silang kanggo terminal sinyal adohmaksimal 1.5 mm2 padhet / fleksibel