Ngaleungitkeun rupa-rupa mérek T1 + T2, Kelas B + C, Kelas I + II, Iimp 12,5kA surge protéksi alat SPD
1. Dehn (Jérman)
1) Dehn - kilat ayeuna sareng surge arrester AC T1 + T2, Kelas B + C, Kelas I + II Iimp 12,5kA alat pelindung surge SPD 1 + 1, 1 + NPE
Jenis: DSH TT 2P 255 FM, Bagian No .: 941110
- Aplikasi-dioptimalkeun sareng prewired spark-gap-based tipe 1 sareng tipe 2 gabungan arus listrik sareng surge arrester
- Desain kompak kusabab téknologi gap spark-save space kalayan lega ngan ukur 1 modul / tiang
- Ngamungkinkeun beungkeutan equipotential kilat kompak kaasup panyalindungan alat terminal
- Aplikasi-dioptimalkeun sareng prewired gabungan kilat ayeuna sareng surge arrester pikeun sistem TT-tahap sareng TN-S fase tunggal (konfigurasi 1 + 1); kalayan kontak sinyal jarak jauh anu ngambang.
SPD numutkeun IEC61643-11: 2011, EN61643-11: 2012 | Kelas I + II, tipe 1 + tipe 2 |
Tegangan nominal (ac) (UN) | 230 V (50/60 Hz) |
Max. tegangan operasi kontinyu (ac) (UC) | 255 V (50/60 Hz) |
Arus dorongan kilat (10/350 μs) [L + N-PE] (Itotal) | 25 Ka |
Arus dorongan kilat (10/350 μs) [LN] / [N-PE] (Iimp) | 12.5/25 kA |
Nomer debit ayeuna (8/20 μs) [LN] / [N-PE] (In) | 12.5/25 kA |
Tingkat panyalindungan tegangan [LN] / [N-PE] (UP) | ≤ 1.5 / ≤ 1.5 kV |
Waktos réspon (tA) | ≤ 100 ns |
Max. panyalindungan arus over-arus utama | 160 a gG |
2) Dehn - kilat sareng arus alat pelindung AC T1 + T2, Kelas B + C, Kelas I + II Iimp 12,5kA alat pelindung surge SPD 3 + 1, 3 + NPE
Jenis: DSH TT 255 FM bagian No. 941315
- Aplikasi-dioptimalkeun sareng prewired spark-gap-based tipe 1 sareng tipe 2 gabungan arus listrik sareng surge arrester
- Desain kompak kusabab téknologi gap spark-save space kalayan lega ngan ukur 1 modul / tiang
- Ngamungkinkeun beungkeutan equipotential kilat kompak kaasup panyalindungan alat terminal
- Aplikasi-dioptimalkeun sareng prewired gabungan arus kilat sareng arrester surge pikeun sistem TT sareng TN-S (konfigurasi 3 + 1); kalayan kontak sinyal jarak jauh anu ngambang
SPD numutkeun IEC61643-11: 2011, EN61643-11: 2012 | Kelas I + II, tipe 1 + tipe 2 |
Tegangan nominal (ac) (UN) | 230 V (50/60 Hz) |
Max. tegangan operasi kontinyu (ac) (UC) | 255 V (50/60 Hz) |
Arus dorongan kilat (10/350 μs) [L1 + L2 + L3 + N-PE] (Itotal) | 50 Ka |
Arus dorongan kilat (10/350 μs) [LN] / [N-PE] (Iimp) | 12.5/50 kA |
Nomer debit ayeuna (8/20 μs) [LN] / [N-PE] (In) | 12.5/50 kA |
Tingkat panyalindungan tegangan [LN] / [N-PE] (UP) | ≤ 1.5 / ≤ 1.5 kV |
Waktos réspon (tA) | ≤ 100 ns |
Max. panyalindungan arus over-arus utama | 160 a gG |
3) Dehn - alat panyalindungan arus sareng lonjakan AC T1 + T2, Kelas B + C, Kelas I + II Iimp 12,5kA alat pelindung surge SPD 4 + 0
Jenis: DSH TNS 255 FM bagian No. 941405
- Aplikasi-dioptimalkeun sareng prewired spark-gap-based tipe 1 sareng tipe 2 gabungan arus listrik sareng surge arrester
- Desain kompak kusabab téknologi gap spark-save space kalayan lega ngan ukur 1 modul / tiang
- Ngamungkinkeun beungkeutan equipotential kilat kompak kaasup panyalindungan alat terminal
- Aplikasi-dioptimalkeun sareng prewired gabungan kilat ayeuna sareng surge arrester pikeun sistem TN-S; kalayan kontak sinyal jarak jauh anu ngambang.
SPD numutkeun IEC61643-11: 2011, EN61643-11: 2012 | Kelas I + II, tipe 1 + tipe 2 |
Tegangan nominal (ac) (UN) | 230 V (50/60 Hz) |
Max. tegangan operasi kontinyu (ac) (UC) | 255 V (50/60 Hz) |
Arus dorongan kilat (10/350 μs) [L1 + L2 + L3 + N-PE] (Itotal) | 50 Ka |
Arus dorongan kilat (10/350 μs) [L, N-PE] (Iimp) | 12.5 Ka |
Nomer debit ayeuna (8/20 μs) [L / N-PE] / [L1 + L2 + L3 + N-PE] (In) | 12.5/50 kA |
Tingkat panyalindungan tegangan [LN] / [N-PE] (UP) | ≤ 1.5 / ≤ 1.5 kV |
Waktos réspon (tA) | ≤ 100 ns |
Max. panyalindungan arus over-arus utama | 160 a gG |
2. Phoenix (Jérman)
Kilat tipe arrester surge 1/2 - VAL-MS-T1 / T2 335 / 12.5 / 3 + 1-FM - 2800183
Universal colokan basis kilat varistor dina arrester kilat / surge pikeun jaringan suplai kakuatan 3-fase sareng N sareng PE misah (sistem 5-konduktor: L1, L2, L3, N, PE), pikeun Perlindungan Kilat Tingkat III sareng IV, kalayan jarak jauh kontak indikasi.
- Kalayan ngambang kontak indikasi jauh
- Panyekel colokan anu aman upami aya beban arus kilat anu tinggi sareng geter anu kuat berkat penambatan anu énggal
- Indikasi status optik, mékanis pikeun panyawat masing-masing
- Pluggable
- Alat pegatkeun sambungan termal pikeun tiap colokan masing-masing
- Coding mékanis sadaya slot
SPD numutkeun IEC61643-11: 2011, EN61643-11: 2012 | Kelas I + II, tipe 1 + tipe 2 |
Tegangan nominal UN 240/415 V AC (TN-S) | 240/415 V AC (TT) 240/415 V AC (TT) |
Frékuénsi nominal fN 50 Hz (60 Hz) | 50 Hz (60 Hz) |
Tegangan operasi kontinyu maksimum UC (LN) | 335V AC |
Tegangan operasi kontinyu maksimum UC (L-PE) | 335V AC |
Tegangan kontinyu maksimum UC (N-PE) | 264V AC |
Dinilai beban ayeuna mahL | 80 A |
Sésana ayeuna mahPE | ≤ 5 μA |
Nominal debit ayeuna Dina (8/20) μs (LN) | 12.5 Ka |
Nominal debit ayeuna Dina (8/20) μs (L-PE) | 12.5 Ka |
Nominal debit ayeuna Dina (8/20) μs (N-PE) | 50 Ka |
Maksimum debit ayeuna Imax (8/20) μs | 50 Ka |
Arus debit impuls (10/350) μs (LN), puncak nilai ayeuna Iimp | 12.5 Ka |
Arus debit impuls (10/350) μs (L-PE), puncak nilai ayeuna Iimp | 12.5 Ka |
Arus debit impuls (10/350) μs (N-PE), puncak nilai ayeuna Iimp | 50 Ka |
Total debit ayeuna mahtotal (8/20) μs | 50 Ka |
Total debit ayeuna mahtotal (10/350) μs | 50 Ka |
Tuturkeun rating gangguan ayeuna kuringfi (N-PE) | 100 A |
Peunteun arus pondok-circuit ISCCR | 25 Ka |
2. Raycap (Jérman)
1) Alat panyalindungan arus sareng lonjakan AC T1 + T2, Kelas B + C, Kelas I + II Iimp 12,5kA alat pelindung gelombang SPD 3 + 1, 3 + NPE
Modél Raycap: Kode urutan ProTec T1-300-3 + 1-R 590060
Kilat sareng Perlindungan Overvoltage 12.5 kA Series
ProTec T1 3 + 1 Kelas I Kelas II Tipe 1 Tipe 2 Tipe 1CA
Lokasi Pamakéan: Papan Distribusi Utama
Sistem Jaringan: TT, TN-S
Mode Perlindungan: LN, N-PE
Kategori IEC / EN / UL: Kelas I + II / Tipe 1 + 2 / Tipe 1CA
Perumahan: Desain Pluggable
Patuh: IEC 61643-11: 2011 / EN 61643-11: 2012 / UL 1449-4th Edition
SPD numutkeun IEC61643-11: 2011, EN61643-11: 2012 | Kelas I + II, tipe 1 + tipe 2 |
Tegangan AC nominal (50/60 Hz) Uo/Un | 240 V |
Max. tegangan operasi kontinyu (LN) UC | 300 V |
Max. tegangan operasi kontinyu (N-PE) UC | 305 V |
Nominal Pelepasan Nominal (8/20 μs) (LN) / (N-PE) In | 20 kA / 50 kA |
Pangiriman Saatos Maksimum (8/20 μs) (LN) / (N-PE) Imax | 50 kA / 100 kA |
Impulse Discharge Current (10/350 μs) (LN) / (N-PE) Iimp | 12,5 kA / 50 kA |
Tingkat Perlindungan Tegangan (LN) / (N-PE) UP | 1500 V / 1500 V |
Waktu réspon tA | <25 ns / <100 ns |
Max. panyalindungan arus over-arus utama | 315 A / 250 A gG |
Peunteun arus pondok-arus (AC) (LN) ISCCR | 25 kA / 50 kA |
2) Alat panyalindungan arus sareng lonjakan kilat AC T1 + T2, Kelas B + C, Kelas I + II Iimp 12,5kA alat pelindung surge SPD 4 + 0
Modél Raycap: Kode urutan ProTec T1-300-4 + 0-R 590042
Kilat sareng Perlindungan Overvoltage 12.5 kA Series
Pluggable multi-kutub SPD ProTec T1 4 + 0 Kelas I Kelas II Tipe 1 Tipe 2 Tipe 1CA
Lokasi Pamakéan: Papan Distribusi Utama
Sistem Jaringan: TN-S
Mode Perlindungan: L-PE, N-PE
Rating Lonjakan: Iimp = 12.5 kA (10/350 μs), In = 12.5 kA (8/20 μs)
Kategori IEC / EN / UL: Kelas I + II / Tipe 1 + 2 / Tipe 1CA
Unsur Pelindung: MOV Énergi Tinggi
Perumahan: Desain Pluggable
Patuh: IEC 61643-11: 2011 / EN 61643-11: 2012 / UL 1449, édisi ka-4
SPD numutkeun IEC61643-11: 2011, EN61643-11: 2012 | Kelas I + II, tipe 1 + tipe 2 |
Tegangan AC nominal (50/60 Hz) Uo/Un | 240 V |
Max. tegangan operasi kontinyu UC | 300 V |
Nominal Pelepasan Nominal (8/20 μs) In | 20 Ka |
Pangiriman Saatos Maksimum (8/20 μs) Imax | 50 Ka |
Ngalirkeun Impulse Ayeuna (10/350 μs) Iimp | 12,5 Ka |
Tegangan Protection Level UP | 1500 V |
Waktu réspon tA | <25 ns |
Max. panyalindungan arus over-arus utama | 315 A / 250 A gG |
Peunteun arus pondok-arus (AC) (LN) ISCCR | 25 kA / 50 kA |
4. Citel (Perancis)
Alat protéktor gelombang AC T1 + T2 + T3, Kelas B + C + D, Kelas I + II + III Iimp 12,5kA, 3 + 1, 3 + NPE
DAC1-13VG-31-275, jumlah bagian: 821730234
SPD numutkeun IEC61643-11: 2011, EN61643-11: 2012 | Kelas I + II + III, T1 + T2 + T3 |
Max. AC tegangan operasi UC | 275 V |
Ngaleupaskeun Nominal Ayeuna 15 * (8/20 μs) impuls In | 20 Ka |
Ngaleupaskeun Maksimum Ayeuna Max. tahan @ 8/20 μs ku tihang Imax | 50 Ka |
Arus dorongan ku tihang Max. tahan 10/350 μs Iimp | 12,5 Ka |
Tahan dina kombinasi gelombang Kelas III tés Uoc | 6 kV |
Tingkat Perlindungan Tegangan @ In (8/20 μs) sareng 6 kV (1.2 / 50 μs) UP | 1,5 kV |
Diterima arus pondok ayeuna mahSCCR | 50 Ka |
5. Hakel (Céko)
Kilat sareng surge arrester / varistor + tabung debit gas / JENIS 1 + 2
Halkel PIVM12,5-275 DS-3 + 1
PIVM12,5-275 / 3 + 1 Vseries mangrupikeun opat kutub, kilat oksistor logam oksid sareng arrester surge, digabungkeun sareng tabung debit gas Jenis 1 + 2 numutkeun ICE EN 61643-11. Panangkep ieu disarankeun pikeun digunakeun dina Konsép Zona Perlindungan Kilat dina wates LPZ 0 - 1 (numutkeun IEC EN 62305), dimana aranjeunna nyayogikeun ngempelkeun equipotential sareng ngaleupaskeun duanana, arus kilat sareng gelombang switching, anu dihasilkeun dina sistem catu daya asup ka gedong. Pamakéan panangkep kilat ayeuna PIVM12,5-275 / 3 + 1 Vseries utamina dina jalur catu daya, anu dioperasikeun salaku sistem TN-S sareng TT. Pamakéan utama PIVM12,5-275 / 3 + 1 Vseries arrester nyaéta dina struktur LPL III-IV numutkeun IEC EN 62305. The marking M khususkeun jinis konstruksi kalayan modul anu tiasa dicabut. Nyirian DS ngahususkeun vérsi kalayan ngawaskeun jauh.
SPD numutkeun IEC61643-11: 2011, EN61643-11: 2012 | Kelas I + II, B + C, T1 + T2 |
Max. tegangan operasi kontinyu UC | 275 V AC / 350 V DC |
Ngaleupaskeun Maksimum Ayeuna 8/20 μs Imax | 50 Ka |
Impuls Kilat ayeuna 10/350 μs (LN) Iimp | 12,5 Ka |
Impuls Kilat ayeuna 10/350 μs (N-PE) Iimp | 50 Ka |
Total kilat ayeuna 10/350 μs [L1 + L2 + L3 + N] -PE | 50 Ka |
Ngaleupaskeun Nominal Ayeuna 8/20 μs In | 20 Ka |
Tegangan Protection Level UP | <1,2 kV |
Waktos réspon L / N | <25 ns |
Waktos réspon N / PE | <100 ns |
Max. sekering deui-up | 160 A gL / gG |
Diterima arus pondok ayeuna mahSCCR | 60 Karms |
Alat panyalindungan lonjakan dianggo salaku panangtayungan pamasangan listrik ngalawan overvoltage samentawis sareng stroke kilat henteu langsung. SPDs ieu didesain sareng disertifikasi numutkeun EN 61643-11. Unit indikasi ngabantosan pangguna pikeun terang status alat sareng port sinyal jauh tiasa nyayogikeun indikasi jauh sareng alarm. Desain modul plug-in matak ngamudahkeun pikeun ngarobih modul anu dianggo tanpa sambungan alat.
Impuls maksimum ayeuna Iimp 12.5 kA (10/350 µs) per fase / 50 kA (10/350 )s) pikeun modul NPE (+1)
Nominal debit ayeuna Dina 25 kA (8/20 µs) per fase / 50 kA (8/20 µs) pikeun modul NPE (+1)
Maksimum debit ayeuna Imax 50 kA (8/20 µs)
Maksimum tegangan operasional kontinyu Uc 275 V AC per fase / 255 V AC pikeun modul NPE (+1)
Kusabab Iimp 12.5 kA per tihang cocog pikeun LPL III sareng LPL IV numutkeun EN 62305 dina standar 3-fase TN-C sareng panginstalan TN-S
Versi kalayan sambungan 1 + 0, 1 + 1, 2 + 0, 3 + 0, 3 + 1 sareng 4 + 0
Desain modul plug-in, Kalayan sareng tanpa kontak indikasi jauh, Indikator status paranti
Hasil analisis primér:
Dehn nganggo celah percikan pikeun ngadamel T1 + T2 Iimp 12.5kA surge protection device SPD.
Phoenix, Raycap, Citel, Hakel, sareng Chint nganggo varistors énergi tinggi (LN) sareng tabung debit gas (N-PE) pikeun ngadamel T1 + T2 SPD.