Mbusak macem-macem merek T1 + T2, Kelas B + C, Kelas I + II, Iimp 25kA perangkat proteksi gelombang SPD
1. Dehn (Jerman)
Dehn kilat saiki lan gelombang arrester DV M TT 2P 255 FM T1 + T2, Kelas B + C, Kelas I + II piranti proteksi gelombang SPD
Jinis: DV M TT 2P 255 FM, No Part: 951115
- Arus bledhek gabungan lan arus arrester sing dipasang ing bunder gabungan, kalebu bagean dhasar lan modul proteksi plug-in
- Kasedhiyan sistem maksimum amarga Aliran RADAX tindakake watesan saiki
- Ora ana tripping 20 A gL / gG sekering nganti 50 kArms arus pendek
- Kapasitas arus kilat saiki: 50 kA (10/350 )s)
- Ngidini kanggo nglindhungi peralatan terminal
- Indikasi kesalahan kanthi tandha abang ing jendela inspeksi
- Ganti modul proteksi kanthi gampang nganggo sistem kunci modul kanthi ngeculake tombol
Arus kilat gabungan lan arus arrester gabungan kanggo nglindhungi sistem TT fase lan TN (sirkuit "1 + 1") saka lonjakan
SPD miturut EN 61643-11 / IEC 61643-11 | jinis 1 + jinis 2 / kelas I + kelas II |
Koordinasi energi karo peralatan terminal (<10 m) | ketik 1 + jinis 2 + jinis 3 |
Voltase nominal (ac) (UN) | 230 V (50/60 Hz) |
Maks. voltase operasi terus (ac) [LN] (UC) | 264 V (50/60 Hz) |
Maks. voltase operasi terus-terusan (ac) [N-PE] (UC (N-PE)) | 255 V (50/60 Hz) |
Arus impuls kilat (10/350 μs) [L + N-PE] (ITotal) | 50 kA |
Arus impuls kilat (10/350 μs) [LN] / [N-PE] (Iimp) | 25/50 kA |
Arus debit nominal (8/20 μs) [LN] / [N-PE] (In) | 25/50 kA |
Dehn DV Series 255 V ac Rating Maksimum Maksimum 100kA Arrester Kilat Mundhak Saiki, DIN Rail Mounting
Jinis: DV M TT 255 FM, No Part: 951315
SPD miturut EN 61643-11 / IEC 61643-11 | jinis 1 + jinis 2 / kelas I + kelas II |
Koordinasi energi karo peralatan terminal (≤ 10 m) | ketik 1 + jinis 2 + jinis 3 |
Voltase nominal (ac) (UN) | 230/400 V (50/60 Hz) |
Maks. voltase operasi terus (ac) [LN] (UC) | 264 V (50/60 Hz) |
Maks. voltase operasi terus-terusan (ac) [N-PE] (UC (N-PE)) | 255 V (50/60 Hz) |
Arus impuls kilat (10/350 μs) [L1 + L2 + L3 + N-PE] (ITotal) | 100 kA |
Arus impuls kilat (10/350 μs) [LN] / [N-PE] (Iimp) | 25/100 kA |
Arus debit nominal (8/20 μs) [LN] / [N-PE] (In) | 25/100 kA |
Dehn 255 V ac 100kA Arrester Kilat DV, Pemasangan Rel DIN
Jinis: DV M TNS 255, Bagian No .: 951400
SPD miturut EN 61643-11 / IEC 61643-11 | jinis 1 + jinis 2 / kelas I + kelas II |
Koordinasi energi karo peralatan terminal (≤ 5 m) | ketik 1 + jinis 2 + jinis 3 |
Voltase nominal (ac) (UN) | 230/400 V (50/60 Hz) |
Maks. voltase operasi terus-terusan (ac) (UC) | 264 V (50/60 Hz) |
Saiki impuls kilat (10/350 )s) [L1 + L2 + L3 + N-PE] (ITotal) | 100 kA |
Arus impuls kilat (10/350 )s) [L, N-PE] (Iimp) | 25 kA |
Arus debit nominal (8/20 )s) [L / N-PE] / [L1 + L2 + L3 + N-PE] (In) | 25/100 kA |
2. Phoenix (Jerman)
Arus kilat Phoenix lan arrester gelombang T1 + T2, Kelas B + C, piranti proteksi gelombang kelas I + II SPD
Perlindhungan mundhak kanggo pasokan listrik
Tipe gabungan 1/2 piranti protèktif - FLT-SEC-P-T1-1S-350/25-FM, pesenan no. 2905415
- Spark gap ora duwe tindakake saiki
- Bebas arus bocor, cocog digunakake ing wilayah pra-meter
- Tegangan terus-terusan 350 V AC kanggo jaringan AC 230/400 V kanthi fluktuasi tegangan tinggi
- Pluggable
- Tingkat proteksi voltase sedheng 1.5 kV
- Indikator status mekanik, optik
- Kanthi kontak pratondo remot ngambang
Klasifikasi tes IEC | I / II, T1 / T2 |
Tegangan nominal UN | 240 V AC (TN-S) 240 V AC (TT) |
Cara nglindhungi | LN / L-PE / N-PE |
Tegangan operasi maksimum maksimum UC | 350 V AC |
Impulse debit saiki akuimp (10/350) s | 25 kA / 25 kA / 100 kA |
Arus debit nominal In (8/20) s | 25 kA / 25 kA / 100 kA |
Maks. debit saiki akumax (8/20) s | 50 kA |
3. Raycap (Jerman) & Iskra Zascite (Slovenia)
Perlindhungan kilat lan overvoltage Kelas I Kelas II Tipe 1 Tipe 2 Tipe 4CA
Ketik: ProTec T1HS-300-3 + 1-R, Kode Pesenan: 59.0307
- Lokasi Panggunaan: Papan Distribusi Utama
- Sistem Jaringan: TT, TN-S
- Cara Proteksi: LN, N-PE
- Kategori IEC / EN / UL: Kelas I + II, Tipe 1 + 2, Tipe 4CA
- Teknologi: Sato
- Bebas Saiki Mbocor: Ya
- Omah: Desain Pluggable
- Kepatuhan: IEC 61643-11: 2011; EN 61643-11: 2012; UL 1449 Edhisi 4
Tegangan AC Nominal (50 / 60Hz) Uo /Un | 240 V |
Tegangan Operasi Maksimum (AC) (LN) / (N-PE) Uc | 300 V / 305 V |
Nominal Saiki Ngirim (8/20 μs) (LN) / (N-PE) In | 25 kA / 100 kA |
Saiki Mbuwang Maksimum (8/20 μs) (LN) / (N-PE) Imax | 65 kA / 130 kA |
Impulse Discharge Current (10/350 μs) (LN) / (N-PE) Iimp | 25 kA / 100 kA |
Energi Sprcific (LN) / (N-PE) W / R | 156.2kJ / Ω / 2500kJ / Ω |
Ngisi daya (LN) / (N-PE) Q | 12.5 Minangka / 50 Minangka |
Tingkat Perlindhungan Tegangan (LN) / (N-PE) Up | 1500 V / 1500 V |
Dinilai Beban SaikiL | 100 A |
Wektu Respon (LN) / (N-PE) tA | <100 ns / <100 ns |
Proteksi Overcurrent (max) | 315 gG |
Rating Saiki Short-Circuit (AC) ISCCR | 50 kA |
Tututi Rating Interrupt Saiki (N-PE) Ifi | 100 ARMS |
TOV Tahan 120min (LN) UT | 442 V |
TOV Tahan 200ms (N-PE) UT | 1200 V |
Jumlah port | 1 |
Tegangan Operasi Maksimum (AC) (L - N) / (N - G) MCOV | 300 V / 305 V |
Ukur Watesan voltase (L - N) / (N - G) MLV | 1280 V / 1000 V |
Nominal Saiki Ngirim (8/20 μs) (L - N) / (N - G) Ing | 20 kA |
Operasi Suhu Operasi Ta | -40 oF nganti +185 oF [-40 oC nganti +85 oC] |
Kelembapan Operasi sing Diidini RH | 5%… 95% |
dhuwur | 13123 ft [4000 m] |
Torsi Sekrup Terminal Mmax | 39.9 Ibf · ing [4.5 Nm] |
Konduktor Salib Konduktor (maks) | 2 AWG (Solid, Straded) / 4 AWG (Fleksibel) |
35 mm2 (Padat, terdampar) / 25 mm2 (Fleksibel) | |
soyo tambah | Rel DIN 35 mm, EN 60715 |
Degree Protection | IP 20 (internal) |
Material Housing | Thermoplastic: Gelar Ngusir UL 94 V-0 |
Perlindhungan termal | Ya |
Indikator Operasi / Kesalahan | Gendéra Ijo / Ora Gendera Ijo |
Kontak Jauh (RC) | pilihan |
Kapasitas Ngalih RC | AC: 250 V / 1A, 125 V / 1 A; DC: 48 V / 0.5 A, 24 V / 0.5 A, 12 V / 0.5 A. |
Seksi Salib Konduktor RC (maks) | 16 AWG (Solid) / 1.5 mm2 (Padhet) |
4. Citel (Prancis)
Tipe 1 + 2 + 3 AC Surge Protector DS250VG seri
Model CITEL: DS250VG-300, Nomer bagean: 2577
- Tipe 1 + 2 + 3 Protector munggah
- 25 kA ing 10/350 μs impuls
- Tegangan endhek UP
- Putus internal, indikator status lan sinyal jarak jauh
- Dioptimalake dadi TOV
- IEC 61643-11 lan EN 61643-11 kepatuhan
- UL 1449 ed. 4 pangenalan
Description | Tipe 1 + 2 + 3 AC protector siji-tiang |
Network | 230 / 400 V |
Maks. Tegangan operasi AC (UC) | 255 Wac |
Charasteristics Voltage Over Voltage (TOV) - 5 sec. (UT) | 335 Vac tahan |
Charasteristics Voltage Over Voltage (TOV) - 120 mn (UT) | 440 Vac tahan |
Sisa saiki - Saiki bocor ing Uc (Ipe) | Ana |
Maks. Muat saiki (yen sambungan sambungan) (IL) | 100 A |
Tututi saiki (If) | Ana |
Arus debit nominal - 15 x 8/20 ul s impulses (In) | 30 kA |
Maks. debit saiki -max. tahan @ 8/20 bys kanthi tiang (Imax) | 70 kA |
Impulse current by pou - maks. tahan 10 / 350µs (Iimp) | 25 kA |
Energi spesifik miturut tiang (W / R) | 156 kJ / ohm |
Tahan ing bentuk gelombang Kombinasi - Tes Kelas III (Uoc) | 20 kV |
Tingkat proteksi @ In (Up-ing) | 1.1 kV |
Tingkat proteksi (Up) | 1.5 kV |
Arus sirkuit cendhak sing bisa ditampa (Isccr) | 50000 A |
Pemisah Thermal | internal |
Tumindak | Jinis sekring gG - 315 A |
Pemecah kesalahan dhasar instalasi | Jinis |
dimensi | ndeleng diagram |
Sambungan karo Jaringan | Kanthi terminal sekrup: 6-35 mm2 / kanthi bis |
Indikator sambungan | 1 indikator mekanik |
Sinyal adoh saka sambungan | output ing kontak pangowahan |
soyo tambah | Rel simetris 35 mm (EN60715) |
suhu Operating | -40 / + 85 ° C |
Rating proteksi | IP20 |
Bahan omah | Termoplastik UL94-V0 |
Selaras karo standar | IEC 61643-11 / EN 61643-11 / UL1449 ed.4 |
Certification | UL / CSA / EAC |
Nomer part | 2577 |
5. Saltek (Ceko)
OEM kanggo Schneider, ayo njupuk conto Schneider kayata.
SPD Tipe 1 - Kilat Saiki Arrester FLP-25-T1-V (S) -3 + 1, nomer pesenan .: A05305
modul pluggable, sinyal kesalahan visual, kunci modul
- kombinasi arrester petir kinerja dhuwur telung tiang lan kesenjangan percikan efisiensi enkapsulasi, disambungake ing mode 3 + 1
- instalasi ing wates zona LPZ 0 lan LPZ 1 utawa luwih dhuwur, utamane menyang papan distribusi utama
- kanggo nglindhungi pengaruh serangan kilat langsung utawa ora langsung ing macem-macem aplikasi - omah, kantor lan bangunan industri
- koordinasi karo SPD Type 2 (SLP-275 V) sanajan tanpa induktor misahake gelombang
- sinyal kesalahan kesalahan adoh (S)
- ora ana arus bocor
Tegangan nominal Un | 230 V AC |
Voltase operasi maksimum LN Uc | 260 V AC |
Tegangan operasi maksimum N-PE Uc | 255 V AC |
Nomer saiki mbukak kanggo sambungan "V" IL | 125 A |
Saiki impuls kilat (10/350 μs) LN Iimp | 25 kA |
Saiki impuls kilat (10/350 μs) N-PE Iimp | 100 kA |
Mode level proteksi voltase LN Up | 1,5 kV |
Mode level proteksi voltase N-PE Up | 1,5 kV |
Mode level proteksi voltase L-PE Up | 2,2 kV |
Kemampuan kanggo memateni N-PE I saiki ing ngisor ikifi | 0,1 kA |
Rating arus arus pendek ISCCR | 50 kA |
Perlindhungan arus maksimum | 250 g / gg |
Proteksi overcurrent maksimum kanggo sambungan "V" | 125 g / gg |
Wektu respons LN ta | 100 ns |
Wektu respons N-PE ta | 100 ns |
Salib-bagean konduktor sing gegandhengan solid (min / max) | 2,5 mm2 / 50 mm2 |
Salib-bagean konduktor sing disambungake terdampar (min / max) | 2,5 mm2 / 35 mm2 |
Indikasi kesalahan LN | lapangan pratondo abang |
Indikasi kesalahan N-PE | ora |
Indikasi jarak jauh | kontak pangowahan bebas potensial |
Kontak pratondho adoh | 250V / 0,5A AC, 250V / 0,1A DC |
Penampang konduktor indikasi remot | 1,5 mm2 |
Degree of protection | IP 20 |
Range suhu operasi (min / max) | -40 ° C / 80 ° C |
soyo tambah | Rel DIN 35 mm |
Miturut standar | EN 61643-11: 2012, IEC 61643-11: 2011 / T1 |
6. Weidmuller (Jerman)
Weidmuller kilat arrester VPU I 1 + 1-R LCF 280V / 25kA (Pesen no. 1351740000)
- Jupuk petir kilat I / II kanggo nggunakake hulu meter listrik
- Kanthi 25 kA (10/350 µs) cocog kanggo zona protèktif I, II, III lan IV (LPL I / II / III / IV)
- Kanthi fungsi ngawasi remot, siji kontak pangowahan
- Diuji miturut IEC 61643-11 kanggo nglindhungi tipe I lan II
- Arrester pluggable
Koleksi | VPU I 1 + 1 R LCF 280V / 25KA |
Situs jeneng | 1351740000 |
versi | Arrester voltase gelombang, voltase kurang, karo kontak remot, bebas bocor-saiki, fase tunggal, IT karo N, IT tanpa N, TN |
Tegangan (AC) | 230 V |
Jinis voltase | AC |
Maks. voltase terus, Uc (AC) | 280 V |
Maks. voltase terus, Uc (N-PE) | 260 V |
Jaringan voltase sithik | Fase tunggal, IT kanthi N, IT tanpa N, TN |
Discharge saiki akun (8 / 20µs) N-PE | 100 kA |
Discharge saiki akumax (8 / 20µs) N-PE | 100 kA |
Discharge saiki akun (8 / 20µs) kabel-PE | 25 kA |
Discharge saiki akumax (8 / 20µs) kabel-PE | 100 kA |
Saiki tes petir Iimp (10/350 )s) (L-PE) | 25 kA |
Saiki tes petir, akuimp (10/350 )s) (N-PE) | 100 kA |
Jangkauan frekuensi, maks. | 60 Hz |
Jangkauan frekuensi, min. | 50 Hz |
Fuse | Ora perlu Fuse ≤250 A gG, 250 A gL (yen sekring> 250 A) |
Rating arus sirkuit cendhak (ISCCR) | 25 kA |
Kapabilitas pemadam saiki sing diterusake Ifi | Ora kasedhiya amarga alasan teknis |
Standards | IEC61643-11, EN61643-11 |
Koordinasi energi (≤10 m) | Tipe I, Tipe II, Tipe III |
Tingkat proteksi Up ing akuN (L / N-PE) | 1.6 kV |
Tingkat proteksi Up ing akuN (N-PE) | 1.6 kV |
Saiki bocor ing Un | 1 µA |
Voltase gelombang sementara (over-voltage) - TOV | 438 V |
Cagak cagak | 1 |
Dinilai beban saiki akuL | 125 A |
Kategori syarat Syarat acc. nganti IEC 61643-11 | Tipe I, Tipe II |
Kelas syarat, acc. nganti EN 61643-11 | T1, T2 |
Respon wektu | ≤ 100 ns |
Kontak sinyal | 250 V 1A 1CO |
Cocog kanggo | Instalasi count-in (bocor saiki gratis) |
Asil analisis utami:
Dehn lan Phoenix nggunakake celah sparks encapsulated kanggo nggawe T1 (T1 + T2) SPD.
Raycap, Citel, Saltek lan Weidmuller nggunakake varistors energi plus tabung debit gas (GDT) kanggo nggawe T1 (T1 + T2) SPD.