Signal wires surge protection device


Dehn – IT systems DIN Rail mounted SPD

DEHN BCO ML2 BE series

Dimension drawing BCO ML2 BE 24

Basic circuit drawing BCO ML2 BE series

BLITZDUCTORconnect – Modular Universal lightning current and surge arrester

  • For protecting measuring and control circuits, bus and telecommunication systems
  • High total discharge capacity of 3 kA (10/350 µs), 10 kA (8/20 µs)
  • Max. impulse current carrying capability (8/20 µs) Imax up to 20 kA
  • Low voltage protection level, also capable of protecting terminal equipment

Arrester consisting of a module and base part

  • Fast and simple cable connection thanks to push-in connection terminals
  • All protection components integrated into the module
  • secR release buttons on both sides for safe module replacement
  • High system availability thanks to the fail-safe performance

Function-optimised design with a width of 6 mm

  • LifeCheck and visual status indication integrated in the module
  • Simple remote signalling of the status with the help of an optional remote signalling unit
  • Tool-free signal disconnection for maintenance purposes
  • Vibration and shock-tested for safe operation

BCO ML2 BE

  • LifeCheck arrester monitoring and integrated status indication
  • Modular two-pole arrester for optimal protection of two single lines
  • For installation in conformity with the lightning protection zone concept at the boundaries from 0A –2 and higher

Space-saving, modular combined arrester with a width of 6 mm and push-in connection technology with status indication for protecting two single lines sharing a common reference potential as well as unbalanced interfaces. With signal disconnection for maintenance purposes.

Technical data

Dehn TypeBCO ML2 BE 12BCO ML2 BE 24BCO ML2 BE 48
Part No.927 222927 224927 225
SPD classTYPE1 P1TYPE1 P1TYPE1 P1
Impulse categoryD1, C1, C2, C3, B2D1, C1, C2, C3, B2D1, C1, C2, C3, B2
Nominal voltage (UN)12 V24 V48 V
Max. continuous operating voltage (d.c.) (UC)15 V33 V54 V
Max. continuous operating voltage (a.c.) (UC)10.6 V23.3 V38.1 V
Nominal current at 70 °C (IL)0.75 A0.75 A0.75 A
D1 Total lightning impulse current (10/350 µs) (Iimp)3 kA3 kA3 kA
D1 Lightning impulse current (10/350 µs) per line (Iimp)1.5 kA1.5 kA1.5 kA
C2 Total nominal discharge current (8/20 µs) (In)10 kA10 kA10 kA
C2 Nominal discharge current (8/20 µs) per line (In)5 kA5 kA5 kA
Voltage protection level line-line for In C2 (Up)≤ 48 V≤ 90 V≤ 140 V
Voltage protection level line-PG for In C2 (Up)≤ 45 V≤ 75 V≤ 90 V
Voltage protection level line-line for In C1 (Up)≤ 48 V≤ 90 V≤ 140 V
Voltage protection level line-PG for In C1 (Up)≤ 45 V≤ 75 V≤ 90 V
Voltage protection level line-line at 1 kV/µs C3 (Up)≤ 38 V≤ 85 V≤ 130 V
Voltage protection level line-PG at 1 kV/µs C3 (UP)≤ 20 V≤ 45 V≤ 68 V
Series resistance per line1 ohm(s)1 ohm(s)1 ohm(s)
Cut-off frequency line-line (fG)1.4 MHz3.4 MHz5 MHz
Operating temperature range (TU)-40 °C … +80 °C-40 °C … +80 °C-40 °C … +80 °C
Operating state / fault indicationgreen / redgreen / redgreen / red
Degree of protectionIP 20IP 20IP 20
Connection (input / output)push-in / push-inpush-in / push-inpush-in / push-in
Cross-sectional area (solid)0.2-2.5 mm20.2-2.5 mm20.2-2.5 mm2
Cross-sectional area (flexible)0.2-2.5 mm20.2-2.5 mm20.2-2.5 mm2
Earthing via35 mm DIN rails acc. to EN 6071535 mm DIN rails acc. to EN 6071535 mm DIN rails acc. to EN 60715
Enclosure materialpolyamide PA 6.6polyamide PA 6.6polyamide PA 6.6
Colouryellowyellowyellow
Test standardsIEC 61643-21 / EN 61643-21IEC 61643-21 / EN 61643-21IEC 61643-21 / EN 61643-21
ApprovalsUL, SILUL, SILUL, SIL
Extended technical data:
– Max. discharge current (8/20 µs) [1/2 – PG], [1+2 – PG] (Imax)20 kA20 kA20 kA
– Discharge current (8/20 µs) [1/2 – PG], [1+2 – PG]10 kA (10x)10 kA (10x)10 kA (10x)
– Voltage protection level line-PG at 1 kV/μs C3 after being subjected to Imax (Up)≤ 20 V≤ 20 V≤ 20 V

Citel – telecom surge protector

CITEL 1-pair monobloc Telecom surge protector DLC Series

Dimension drawing CITEL 1-pair monobloc Telecom surge protector DLC Series

Basic circuit diagram CITEL 1-pair monobloc Telecom surge protector DLC Series

1-PAIR MONOBLOC TELECOM SURGE PROTECTOR DLC SERIES

  • For ‘DIN’ rail mounting
  • All types of Telephone and Data lines
  • Monobloc housing and very compact
  • Protection of shield wire
  • IEC 61643-21 compliance

DLC compact surge protectors are designed to protect, against surge voltages due to lightning, terminals equipment connected to industrial buses, telecom lines, or data lines. These surge protectors must be installed on symmetrical DIN rail or on the modular panels and are available for most of the transmission lines These products are 1-pair surge protectors with monobloc enclosure

Technical data

CITEL ModelDLC-170DLC-48DBCDLC-48D3DLC-24D3DLC-12D3DLC-06DBCDLC-06D3
Description1-pair monobloc Telecom surge protector1-pair monobloc Telecom surge protector1-pair monobloc Telecom surge protector1-pair monobloc Telecom surge protector1-pair monobloc Telecom surge protector1-pair monobloc Telecom surge protector1-pair monobloc Telecom surge protector
NetworkTelephone line,ADSL2, VDSL2Fipway, World-FIP, FieldBus-H2ISDN-T0, Line 48VLS, 4-20mARS232, RS485MIC/T2, 10BaseTRS422
SPD configuration1-pair + shielded1-pair + shielded1-pair + shielded1-pair + shielded1-pair + shielded1-pair + shielded1-pair + shielded
Nominal line voltageUn150 V48 V48 V24 V12 V6 V6 V
Max. DC operating voltageUc170 V53 V53 V28 V15 V8 V8 V
Max. Load currentIL300 mA300 mA300 mA300 mA300 mA300 mA300 mA
Max. frequencyf max> 10 MHz> 20 MHz> 3 MHz> 3 MHz> 3 MHz> 20 MHz> 3 MHz
Insertion loss @ fmax< 1 dB< 1 dB< 1 dB< 1 dB< 1 dB< 1 dB< 1 dB
Nominal discharge current

8/20µs Test x 10 – C2 Category

In5 kA5 kA5 kA5 kA5 kA5 kA5 kA
Max. discharge current -max. withstand @ 8/20 µs by poleImax10 kA10 kA10 kA10 kA10 kA10 kA10 kA
Impulse current

2 x 10/350µs Test – D1 Category

Iimp2.5 kA2.5 kA2.5 kA2.5 kA2.5 kA2.5 kA2.5 kA
Protection level

following C3 Category test

Up220 V70 V70 V40 V30 V25 V25 V
Failsafe behaviorShort-circuitShort-circuit
Mechnical characteristics
Dimensionssee diagramsee diagram
FormatDIN boxDIN box
Connection to Networkby spring – max. cross section 1.5 mm2by spring – max. cross section 1.5 mm2
Disconnection indicatortransmission interrupt -default mode 2transmission interrupt -default mode 2
MountingSymmetrical rail DIN 35 mm (EN60715)Symmetrical rail DIN 35 mm (EN60715)
Operating temperature-40/+85°C-40/+85°C
Protection ratingIP20IP20
Housing materialThermoplastic UL94-V0Thermoplastic UL94-V0
Standards
ComplianceIEC 61643-21 / EN 61643-21 / UL497AIEC 61643-21 / EN 61643-21 / UL497A
Part number641105641114641104641103641102641111641101

Phoenix – signal wires surge protection device

Surge protection device - TTC-6-2X1-24DC-PT - 2906805

Dimension drawing TTC-6-2X1-24DC-PT

Basic circuit drawing TTC-6-2X1-24DC-PT

TC-6-2X1-24DC-PT – 2906805

Surge protection for two signal wires with common reference potential, e.g., Digital IN/OUT.

  • Space-saving and cost-saving with a narrow overall width of just 6 mm
  • Quick and tool-free installation of surge protective devices, thanks to Push-in connection technology
  • Finding the right product for all possible requirements in MCR applications is easy, thanks to the complete range of products with customized features

Technical data

TypeTTC-6-2X1-24DC-PT
Ambient conditions
Ambient temperature (operation)-40 °C … 85 °C
Ambient temperature (storage/transport)-40 °C … 85 °C
Permissible humidity (operation)5 % … 95 %
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20
General
Housing materialPBT
Flammability rating according to UL 94V-0
Colortraffic grey A RAL 7042
Mounting typeDIN rail: TH 35 – 7.5 mm
TypeDIN rail module, one-piece
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Protective circuit
IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
21 V DC
Rated current600 mA (40 °C)
Operating effective current IC at UC≤ 5 µA
Residual current IPE≤ 10 µA
Nominal discharge current In (8/20) µs (line-earth)5 kA
Pulse discharge current Iimp (10/350) µs (line-earth)0.5 kA
Total discharge current Itotal (8/20) µs10 kA
Voltage protection level Up (line-earth)≤ 140 V (C1 – 1 kV / 500 A)
≤ 130 V (C2 – 10 kV / 5 kA)
≤ 45 V (C3 – 25 A)
≤ 50 V (C3 – 100 A)
Voltage protection level Up static (line-earth)≤ 55 V (C1 – 1 kV / 500 A)
≤ 80 V (C2 – 10 kV / 5 kA)
Response time tA (line-earth)≤ 1 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 270 kHz/150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 960 kHz
Capacity (line-earth)typ. 2.2 nF
Protective circuit
Resistance per path1.65 Ω ±20 %
Surge protection fault messagenone
Max. required back-up fuse630 mA (FF)
Impulse durability (line-earth)C1 – 1 kV / 500 A
C2 – 10 kV / 5 kA
C3 – 100 A
D1 – 500 A
Pulse reset time (line-earth)≤ 300 ms
Additional technical data
Max. total discharge current I total max (8/20) µs20 kA (1x)
Connection data
Connection methodPush-in connection
Stripping length8 mm
Conductor cross section flexible0.2 mm2 … 2.5 mm2
Conductor cross section solid0.2 mm2 … 4 mm2
Conductor cross section AWG24 … 12
Standards and Regulations
Standards/specificationsIEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013

Saltek – data line surge protection

DM-...-1-RB

Dimension drawing DM-...-1-RB

Basic circuit drawing DM-...-1-RB

DM-…/1-RB

  • Coarse and fine surge protection for telecommunications and signalling network, ST2+3 in terminal block coupling impedance (resistance), screwless terminals
  • coarse and fine surge protection for 2-core signalling networks
  • installation close to protected equipment
  • for protection of communication interfaces, mainly the RS-485 lines, of I&C, electronic security and fire detection systems, etc. against impact of surge voltage
  • coarse and fine surge protection in differential mode (core – core) and common mode (core – PE)

Technical data

Parameter / TypeDM-006/1-RBDM-012/1-RBDM-024/1-RBDM-048/1-RB
Connection (input – output)screwless terminalsscrewless terminalsscrewless terminalsscrewless terminals
Location of SPDST 2+3ST 2+3ST 2+3ST 2+3
Nominal voltageUn6 V DC12 V DC24 V DC48 V DC
Maximum operating voltageUc6 V AC / 8,5 V DC11 V AC / 16 V DC25 V AC / 36 V DC36 V AC / 51 V DC
Nominal load currentIL0,5 A0,5 A0,5 A0,5 A
C2 nominal discharge current (8/20 µs) per coreIn5 kA5 kA5 kA5 kA
C2 total discharge current (8/20 µs) cores-PEITotal10 kA10 kA10 kA10 kA
D1 impulse discharge current (10/350 µs) per coreIimp0,5 kA0,5 kA0,5 kA0,5 kA
C2 voltage protection level mode core-core at InUp18 V28 V50 V80 V
C2 voltage protection level mode

core-PE at In

Up30 V40 V65 V95 V
C3 voltage protection level mode

core-core at 1 kV/µs

Up12 V20 V45 V65 V
C3 voltage protection level mode

core-PE at 1 kV/µs

Up15 V20 V45 V65 V
Response time core-coreta1 ns1 ns1 ns1 ns
Response time core-PEta1 ns1 ns1 ns1 ns
Serial resistance per coreR1,6 Ω1,6 Ω1,6 Ω1,6 Ω
Treshold frequency core-coref1 MHz2 MHz4 MHz5 MHz
Cross-section of connected conductors solid (min/max)0,08 mm2 / 4 mm20,08 mm2 / 4 mm20,08 mm2 / 4 mm20,08 mm2 / 4 mm2
Cross-section of connected conductors stranded (min/max)0,08 mm2 / 2,5 mm20,08 mm2 / 2,5 mm20,08 mm2 / 2,5 mm20,08 mm2 / 2,5 mm2
Degree of protectionIP 20IP 20IP 20IP 20
Range of operating temperatures

(min/max)

-40 °C / 70 °C-40 °C / 70 °C-40 °C / 70 °C-40 °C / 70 °C
MountingDIN rail 35 mmDIN rail 35 mmDIN rail 35 mmDIN rail 35 mm
According to standardEN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 / C2,C3EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 / C2,C3EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 / C2,C3EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 / C2,C3
Ordering numberA06057A06058A06059A06060

Learn more replaceable products FRD2 series