Surge protection for 5G cell site (mobile base station)


Protecting the power supply
Avoid false tripping of systems fuses
The infrastructure in main and system power supplies is protected by proven combined lightning current and surge arresters.
DEHN combined arresters are characterized by a particularly high follow current extinguishing capability and follow current limiting capacity. This avoids false tripping of system fuses that would lead to the disconnection of mobile radio systems. For you, this means particularly high system availability.

Product recommendation
Universally applicable – independent of the feeding grid system
DEHNvap protects the 230/400 V power supply of cell sites.
This combined arrester is universally applicable, independently of the supplying grid system:
All DEHNvap versions reliably protect TT and TN-S systems (3+1 configuration).

DEHNvap NG
Specially developed for mobile communication systems and “ready for 5G”. The pluggable combined arrester for three-phase TT and TNS systems protects the power supply in just 4 modules.

  • Prewired type 1 + type 2 spark-gap-based combined arrester, optimized for protecting mobile radio systems
  • Maximum system availability thanks to Rapid Arc Control / RADAX Flow follow current limitation
  • Discharge capacity up to 100 kA (10/350 µs)
  • No tripping of 32 A gG fuses up to short-circuit currents of 25 kArms
  • Protection of terminal devices within 10m
  • Visual status indication integrated in the module (green = ok, red = faulty); status is signalled via remote signalling contact
  • Different products tailored to the specific requirements of mobile radio systems

DVA M NG 3P 100 FM, Part No. 900352, GTIN 4013364455931, Customs tariff No.: 85363090

DEHNvap DVA M NG 3P 100 FM

Basic circuit diagram DVA M NG 3P 100 FM

Dimension drawing DVA M NG 3P 100 FM

DVA M NG 3P 100 FM (900 352)

  • Prewired, spark-gap-based type 1 + type 2 combined lightning current and surge arrester consisting of a base part and plug-in protection module
  • Compact unit fulfils maximum safety requirements thanks to Rapid Arc Control (RAC)
  • Capable of protecting terminal equipment
  • Modular combined arrester for TT and TN-S systems (3+1 circuit).

Technical data

SPD according to EN 61643-11 / … IEC 61643-11type 1 + type 2 / class I + class II
Energy coordination with terminal equipment (≤ 10 m)type 1 + type 2 + type 3
Nominal voltage (a.c.) (UN)230 / 400 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.)[L-N]/[N-PE] (UC)255 V (50 / 60 Hz)
Lightning impulse current (10/350 μs) [L1+L2+L3+N-PE] (Itotal)100 kA
Specific energy [L1+L2+L3+N-PE] (W/R)2.50 MJ/ohms
Nominal discharge current (8/20 μs) (In)25 / 100 kA
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp)25 / 100 kA
Specific energy [L-N]/[N-PE] (W/R )156.25 kJ/ohms / 2.50 MJ/ohms
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In)25 / 100 kA
Voltage protection level [L-N] / [N-PE] (UP)≤ 1.5 kV / ≤ 1.5 kV
Follow current extinguishing capability [L-N]/[N-PE] (Ifi)25 kArms / 100 Arms
Follow current limitation/SelectivityNo tripping of a 32 A gGfuse up to 25 kArms (prosp.)Response time
Response time (tA)≤ 100 ns
Max. backup fuse (L) up to IK>50kArms250 A gG
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic440 V / 120 min. – withstand
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic1200 V / 200 ms – withstand
Additional abnormal voltage test: 485 V AC / 50 Hz for 24 hwithstand
Let-Through-Energy in combination with an MOV S20K275 (Iimp=2.5 … 25 kA)<1 J
Operating temperature range [parallel]/[series] (TU)-40°C…+80°C / -40 °C … +60 °C
Cross-sectional area (L1, L2, L3, N, PE,) (min.)10 mm2 solid / flexible
Cross-sectional area (L1, L2, L3, N, PE,) (max.)35 mm2 stranded / 25 mm2 flexible
For mounting on35 mm DIN rails acc. to EN 60715
Enclosure materialthermoplastic, red, UL 94 V-0
Place of installationindoor installation
Degree of protectionIP 20
Capacity4 module(s), DIN 43880
ApprovalsKEMA
Type of remote signalling contactchangeover contact
Switching capacity (a.c.)250 V / 0.5 A
Switching capacity (d.c.)250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signalling terminalsmax. 1.5 mm2 solid / flexible

DVA M NG 1P 50 FM, Part No. 900351, GTIN 4013364455948, Customs tariff No.: 85363090

DEHNvap DVA M NG 1P 50 FM

Basic circuit diagram DVA M NG 1P 50 FM

Dimension drawing DVA M NG 1P 50 FM

DVA M NG 1P 50 FM (900 351)

  • Prewired, spark-gap-based type 1 + type 2 combined lightning current and surge arrester consisting of a base part and plug-in protection module
  • Compact unit fulfils maximum safety requirements thanks to Rapid Arc Control (RAC)
  • Capable of protecting terminal equipment
  • Modular combined arrester for single-phase TT and TN systems (1+1 circuit).

Technical data

SPD according to EN 61643-11 / … IEC 61643-11type 1 + type 2 / class I + class II
Energy coordination with terminal equipment (≤ 10 m)type 1 + type 2 + type 3
Nominal voltage (a.c.) (UN)230 (50 / 60 Hz)
Max. continuous operating voltage (a.c.)[L-N]/[N-PE] (UC)255 V (50 / 60 Hz)
Lightning impulse current (10/350 μs) [L +N-PE] (Itotal)50 kA
Specific energy [L+N-PE] (W/R)625.00 kJ/ohms
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp)25 / 50 kA
Specific energy [L-N]/[N-PE] (W/R)156.25 / 625.00 kJ/ohms
Nominal discharge current (8/20 μs) [L-N]/[N-PE] (In)25 / 50 kA
Voltage protection level [L-N] / [N-PE] (UP)≤ 1.5 kV / ≤ 1.5 kV
Follow current extinguishing capability [L-N]/[N-PE] (Ifi)25 kArms / 100 Arms
Follow current limitation/SelectivityNo tripping of a 32 A gGfuse up to 25 kArms (prosp.) Response time
Response time (tA)≤ 100 ns
Max. backup fuse (L) up to IK> 50 kArms250 A gG
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic440 V / 120 min. – withstand
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic1200 V / 200 ms – withstand
Let-Through-Energy in combination with an MOV S20K275 (Iimp=2.5 … 25 kA)< 1 J
Operating temperature range [parallel]/[series] (TU)-40°C…+80°C / -40 °C … +60 °C
Operating state/fault indicationgreen / red
Number of ports1
Cross-sectional area (L1, N, PE,) (min.)10 mm2 solid / flexible
Cross-sectional area (L1, N, PE,) (max.)35 mm2 stranded / 25 mm2 flexible
For mounting on35 mm DIN rails acc. to EN 60715
Enclosure materialthermoplastic, red, UL 94 V-0
Place of installationindoor installation
Degree of protectionIP 20
Capacity2 module(s), DIN 43880
ApprovalsKEMA
Type of remote signalling contactchangeover contact
Switching capacity (a.c.)250 V / 0.5 A
Switching capacity (d.c.)250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signalling terminalsmax. 1.5 mm2 solid / flexible