Disassembling various brand T1+T2, Class B+C, Class I+II, Iimp 12,5kA surge protective device SPD


1. Dehn (Germany)

1) Dehn – lightning current and surge arrester AC T1+T2, Class B+C, Class I+II Iimp 12,5kA surge protective device SPD 1+1, 1+NPE

DEHN - surge protection DSH TT 2P 255 FM part no. 941115

Basic circuit diagram DEHN - surge protection DSH TT 2P 255 FM part no. 941115

DEHN - T1+T2 B+C I+II surge protection DSH TT 2P 255 FM part no. 941115

Type: DSH TT 2P 255 FM, Part No.: 941110

  • Application-optimized and prewired spark-gap-based type 1 and type 2 combined lightning current and surge arrester
  • Compact design due to space-saving spark gap technology with a width of only 1 module/pole
  • Allows compact lightning equipotential bonding including protection of terminal equipment
  • Application-optimized and prewired combined lightning current and surge arrester for single-phase TT and TN-S systems (1+1 configuration); with floating remote signalling contact.

SPD according to IEC61643-11:2011, EN61643-11:2012Class I+II, type 1 + type 2
Nominal voltage (a.c.) (UN)230 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) (UC)255 V (50 / 60 Hz)
Lightning impulse current (10/350 μs) [L+N-PE] (Itotal)25 kA
Lightning impulse current (10/350 μs) [L-N]/[N-PE] (Iimp)12.5 / 25 kA
Nominal discharge current (8/20 μs) [L-N]/[N-PE] (In)12.5 / 25 kA
Voltage protection level [L-N]/[N-PE] (UP)≤ 1.5 / ≤ 1.5 kV
Response time (tA)≤ 100 ns
Max. mains-side overcurrent protection160 A gG

2) Dehn – lightning current and surge protective device AC T1+T2, Class B+C, Class I+II Iimp 12,5kA surge protective device SPD 3+1, 3+NPE

DEHN - surge protection device T1+T2 B+C I+II DSH TT 255 FM part no. 941315

Basic circuit diagram DEHN - surge protection DSH TT 255 FM part no. 941315

Type: DSH TT 255 FM part no. 941315

  • Application-optimized and prewired spark-gap-based type 1 and type 2 combined lightning current and surge arrester
  • Compact design due to space-saving spark gap technology with a width of only 1 module/pole
  • Allows compact lightning equipotential bonding including protection of terminal equipment
  • Application-optimised and prewired combined lightning current and surge arrester for TT and TN-S systems (3+1 configuration); with floating remote signalling contact

SPD according to IEC61643-11:2011, EN61643-11:2012Class I+II, type 1 + type 2
Nominal voltage (a.c.) (UN)230 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) (UC)255 V (50 / 60 Hz)
Lightning impulse current (10/350 μs) [L1+L2+L3+N-PE] (Itotal)50 kA
Lightning impulse current (10/350 μs) [L-N]/[N-PE] (Iimp)12.5 / 50 kA
Nominal discharge current (8/20 μs) [L-N]/[N-PE] (In)12.5 / 50 kA
Voltage protection level [L-N]/[N-PE] (UP)≤ 1.5 / ≤ 1.5 kV
Response time (tA)≤ 100 ns
Max. mains-side overcurrent protection160 A gG

3) Dehn – lightning current and surge protection device AC T1+T2, Class B+C, Class I+II Iimp 12,5kA surge protective device SPD 4+0

DEHN - surge protective device T1+T2 B+C I+II DSH TNS 255 FM part no. 941405

Basic circuit diagram DEHN - surge protective device T1+T2 B+C I+II DSH TNS 255 FM part no. 941405

Type: DSH TNS 255 FM part no. 941405

  • Application-optimized and prewired spark-gap-based type 1 and type 2 combined lightning current and surge arrester
  • Compact design due to space-saving spark gap technology with a width of only 1 module/pole
  • Allows compact lightning equipotential bonding including protection of terminal equipment
  • Application-optimized and prewired combined lightning current and surge arrester for TN-S systems; with floating remote signalling contact.

SPD according to IEC61643-11:2011, EN61643-11:2012Class I+II, type 1 + type 2
Nominal voltage (a.c.) (UN)230 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) (UC)255 V (50 / 60 Hz)
Lightning impulse current (10/350 μs) [L1+L2+L3+N-PE] (Itotal)50 kA
Lightning impulse current (10/350 μs) [L, N-PE] (Iimp)12.5 kA
Nominal discharge current (8/20 μs) [L/N-PE]/[L1+L2+L3+N-PE]

(In)

12.5 / 50 kA
Voltage protection level [L-N]/[N-PE] (UP)≤ 1.5 / ≤ 1.5 kV
Response time (tA)≤ 100 ns
Max. mains-side overcurrent protection160 A gG

2. Phoenix (Germany)

Lightning surge arrester type 1/2 – VAL-MS-T1/T2 335/12.5/3+1-FM – 2800183

phoenix contact lightning surge arrester type 1 type 2 - VAL-MS-T1T2 335 Iimp 12.5 3+1-FM-2800183

surge-arrester-phoenix-contact-val-ms-t1-t2-335-125-11-fm-280018

Basic circuit diagram surge-protection-phoenix-contact-val-ms-t1-t2-335-125-11-fm-280018

surge-protection-phoenix-contact-val-ms-t1-t2-335-125-11-fm-280018

Universal varistor-based plug-in lightning/surge arrester for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), for Lightning Protection Levels III and IV, with remote indication contact.

  • With floating remote indication contact
  • A secure hold of plugs in the event of high lightning current loads and strong vibrations thanks to new latching
  • Optical, mechanical status indication for the individual arresters
  • Pluggable
  • Thermal disconnect device for each individual plug
  • Mechanical coding of all slots

SPD according to IEC61643-11:2011, EN61643-11:2012Class I+II, type 1 + type 2
Nominal voltage UN 240/415 V AC (TN-S)240/415 V AC (TT) 240/415 V AC (TT)
Nominal frequency fN 50 Hz (60 Hz)50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N)335 V AC
Maximum continuous operating voltage UC (L-PE)335 V AC
Maximum continuous voltage UC (N-PE)264 V AC
Rated load current IL80 A
Residual current IPE≤ 5 μA
Nominal discharge current In (8/20) μs (L-N)12.5 kA
Nominal discharge current In (8/20) μs (L-PE)12.5 kA
Nominal discharge current In (8/20) μs (N-PE)50 kA
Maximum discharge current Imax (8/20) μs50 kA
Impulse discharge current (10/350) μs (L-N), peak current value Iimp12.5 kA
Impulse discharge current (10/350) μs (L-PE), peak current value Iimp12.5 kA
Impulse discharge current (10/350) μs (N-PE), peak current value Iimp50 kA
Total discharge current Itotal (8/20) μs50 kA
Total discharge current Itotal (10/350) μs50 kA
Follow current interrupt rating Ifi (N-PE)100 A
Short-circuit current rating ISCCR25 kA

2.  Raycap (Germany)

1) Lightning current and surge protector device AC T1+T2, Class B+C, Class I+II Iimp 12,5kA surge protective device SPD 3+1, 3+NPE

Raycap - ProTec T1-300-3+1-R order code 590060

Basic circuit diagram Raycap - ProTec T1-300-3+1-R order code 590060

Raycap - ProTec T1H-300-3+1-R order code 590321

Raycap Model: ProTec T1-300-3+1-R order code 590060

Lightning and Overvoltage Protection 12.5 kA Series
ProTec T1 3+1 Class I Class II Type 1 Type 2 Type 1CA
Location of Use: Main Distribution Boards
Network Systems: TT, TN-S
Mode of Protection: L-N, N-PE
IEC/EN/UL Category: Class I+II / Type 1+2 / Type 1CA
Housing: Pluggable Design
Compliance: IEC 61643-11:2011 / EN 61643-11:2012 / UL 1449-4th Edition

SPD according to IEC61643-11:2011, EN61643-11:2012Class I+II, type 1 + type 2
Nominal AC voltage (50 / 60 Hz) Uo/Un240 V
Max. continuous operating voltage (L-N) UC300 V
Max. continuous operating voltage (N-PE) UC305 V
Nominal Discharge Current (8/20 μs) (L-N)/(N-PE) In20 kA / 50 kA
Maximum Discharge Current (8/20 μs) (L-N)/(N-PE) Imax50 kA / 100 kA
Impulse Discharge Current (10/350 μs) (L-N)/(N-PE) Iimp12,5 kA / 50 kA
Voltage Protection Level (L-N)/(N-PE) UP1500 V / 1500 V
Response time tA< 25 ns / < 100 ns
Max. mains-side overcurrent protection315 A / 250 A gG
Short-Circuit Current Rating (AC) (L-N) ISCCR25 kA / 50 kA

2) Lightning current and surge protector device AC T1+T2, Class B+C, Class I+II Iimp 12,5kA surge protective device SPD 4+0

Raycap - ProTec T1-300-4+0-R order code 590042

Basic circuit diagram Raycap - ProTec T1-300-4+0-R order code 590042

Raycap Model: ProTec T1-300-4+0-R order code 590042

Lightning and Overvoltage Protection 12.5 kA Series
Pluggable multi-pole SPD ProTec T1 4+0 Class I Class II Type 1 Type 2 Type 1CA
Location of Use: Main Distribution Boards
Network Systems: TN-S
Mode of Protection: L-PE, N-PE
Surge Ratings: Iimp = 12.5 kA (10/350 μs), In = 12.5 kA (8/20 μs)
IEC/EN/UL Category: Class I+II / Type 1+2 / Type 1CA
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance: IEC 61643-11:2011 / EN 61643-11:2012 / UL 1449, 4th edition

SPD according to IEC61643-11:2011, EN61643-11:2012Class I+II, type 1 + type 2
Nominal AC voltage (50 / 60 Hz) Uo/Un240 V
Max. continuous operating voltage UC300 V
Nominal Discharge Current (8/20 μs) In20 kA
Maximum Discharge Current (8/20 μs) Imax50 kA
Impulse Discharge Current (10/350 μs) Iimp12,5 kA
Voltage Protection Level UP1500 V
Response time tA< 25 ns
Max. mains-side overcurrent protection315 A / 250 A gG
Short-Circuit Current Rating (AC) (L-N) ISCCR25 kA / 50 kA

4. Citel (France)

AC surge protector device T1+T2+T3, Class B+C+D, Class I+II+III Iimp 12,5kA, 3+1, 3+NPE

AC surge protector device T1+T2+T3, Iimp 12,5kA DAC1-13VG-31-275, part number 821730234

Basic circuit diagram AC surge protector device T1+T2+T3, Iimp 12,5kA DAC1-13VG-31-275, part number 821730234

DAC1-13VG-31-275, part number: 821730234

SPD according to IEC61643-11:2011, EN61643-11:2012Class I+II+III, T1+T2+T3
Max. AC operating voltage UC275 V
Nominal Discharge Current 15 * (8/20 μs) impulses In20 kA
Maximum Discharge Current

Max. withstand @ 8/20 μs by pole Imax

50 kA
Impulse current by pole

Max. withstand 10/350 μs Iimp

12,5 kA
Withstand on  Combination waveform Class III test Uoc6 kV
Voltage Protection Level @ In (8/20 μs) and 6 kV (1.2/50 μs) UP1,5 kV
Admissible short-circuit current ISCCR50 kA

5. Hakel (Czech)

Lightning and surge arrester / varistor + gas discharge tube / TYPE 1+2

Halkel lightning and surge arrester T1+T2 B+C Iimp 12.5kA PIVM12,5-275 DS-3+1

Basic circuit diagram Halkel PIVM12,5-275 DS-3+1

Halkel PIVM12,5-275 DS-3+1

PIVM12,5-275/3+1 Vseries is a four-pole, metal oxide varistor lightning and surge arrester, combined with gas discharge tube Type 1+2 according to ICE EN 61643-11. These arresters are recommended for use in the Lightning Protection Zones Concept at the boundaries of LPZ 0 – 1 (according to IEC EN 62305), where they provide the equipotential bonding and discharge of both, the lightning current and the switching surge, which are generated in power supply systems entering the building. The use of the lightning current arresters PIVM12,5-275/3+1 Vseries is mainly in the power supply lines, which are operated as TN-S and TT systems. The main use of PIVM12,5-275/3+1 Vseries arrester is in structures of LPL III-IV according to IEC EN 62305. The marking M specifies a type of construction with a removable module. The marking of DS specifies a version with remote monitoring.

SPD according to IEC61643-11:2011, EN61643-11:2012Class I+II, B+C, T1+T2
Max. continuous operating voltage UC275 V AC / 350V DC
Maximum Discharge Current 8/20 μs Imax50 kA
Lightning Impulse current 10/350 μs (L-N) Iimp12,5 kA
Lightning Impulse current 10/350 μs (N-PE) Iimp50 kA
Total lightning current 10/350 μs [L1+L2+L3+N]-PE50 kA
Nominal Discharge Current 8/20 μs In20 kA
Voltage Protection Level UP< 1,2 kV
Response time L/N< 25 ns
Response time N/PE< 100 ns
Max. back-up fuse160 A gL/gG
Admissible short-circuit current ISCCR60 kArms

6. Chint (China)

Type 1+2 SPDs (Class I+II, T1+T2, B+C) complete devices, Iimp = 12.5 kA (10/350 µs)

Chint AC Surge protector device t1+t2 class b+c Iimp 12.5kA

NXU-I+II/F12.5/275V

Surge protection devices are used as a protection of electrical installations against transient overvoltage and indirect lightning strokes. These SPDs are designed and certified according to EN 61643-11. The indication unit helps users to know the status of device and remote-signal port is able to provide remote indication and alarm. Plug-in module design makes it convenient to change the used modules without device disconnection.

Maximum impulse current Iimp 12.5 kA (10/350 µs) per phase / 50 kA (10/350 µs) for NPE (+1) module

Nominal discharge current In 25 kA (8/20 µs) per phase / 50 kA (8/20 µs) for NPE (+1) module

Maximum discharge current Imax 50 kA (8/20 µs)

Maximum continuous operational voltage Uc 275 V AC per phase / 255 V AC for NPE (+1) module

Due to Iimp 12.5 kA per pole suitable for LPL III and LPL IV according to EN 62305 in standard 3-phase TN-C and TN-S installations

Versions with 1+0, 1+1, 2+0, 3+0, 3+1 and 4+0 connection

Plug-in module design, With and without remote indication contact, Device status indicator

Primary analysis result:

Dehn uses a spark gap to make T1+T2 Iimp 12.5kA surge protective device SPD.

Phoenix, Raycap, Citel, Hakel, and Chint use high energy varistors (L-N) and gas discharge tube (N-PE) to make T1+T2 SPD.